Commercial Hot-Water Breakdown: Restoring Supply to a Central London Hospitality Site
A Central London hospitality site lost hot water at every outlet. The plant serving the building included two hot-water cylinders with electric immersion elements, inlet control valves and a recirculation pump.
AH Control found faults in both inlet control valves and the recirculation pump. After sourcing and fitting replacements, we checked the incoming cold-water feed and found that neither cylinder was receiving mains water.
Further investigation identified trapped air in the pipework and check valves stuck closed under back pressure. We cleared the airlock, freed the check valves and confirmed that both cylinders had a water supply. We then refilled and vented the system, checked the pressures and verified that all immersion elements operated.
With the safety checks complete, the hot-water system was returned to service and the site regained hot water. Checking the water supply after the component replacements was what uncovered the remaining fault.