top of page
Search

Industrial Biogas Burner Breakdown & Repair – Sewage Treatment Facility

AH Control Ltd
Oct 26
1 min read

AH Control Ltd resolved repeated biogas burner lockouts at an industrial sewage treatment facility. The Dunphy dual-fuel burner uses biogas produced on site, with diesel as backup.


Dunphy industrial burner at sewage treatment facility

The breakdown


During biogas operation the burner repeatedly locked out on butterfly valve movement errors. The customer faced reliance on purchased diesel instead of using biogas recovered from the treatment process.


Fault diagnosis


Investigation confirmed the servo motor was working correctly, but the biogas butterfly valve was completely seized. Biogas contaminants, including moisture and hydrogen sulphide, can contribute to corrosion, deposits and mechanical sticking.


Biogas butterfly valve and actuator

The repair


We removed the butterfly valve, cleaned and lubricated its appropriate moving components, then refitted it with the existing servo motor. Using burner commissioning mode, we tested movement across the required operating range and returned the boiler to service on biogas.


Siemens butterfly valve removed for repair

The result


Biogas operation was successfully restored. This reduced reliance on expensive diesel backup fuel and avoided unnecessary replacement of a serviceable servo motor.


Dunphy burner combustion controls

Preventing future biogas valve failures


We recommend a planned inspection and maintenance programme for the biogas fuel train, tailored to gas quality, operating hours and manufacturer instructions. Checks should include valve travel and actuator feedback, mechanical resistance, evidence of deposits or corrosion, gas filtration and condensate management, and trend reviews of burner movement faults. Valve cleaning and lubrication must only use materials and procedures approved for the particular valve and biogas service. After any work, appropriate tightness, safety interlock and combustion checks should be completed by competent engineers before return to service.