Industrial Biogas Burner Breakdown & Repair – Sewage Treatment Facility
AH Control Ltd resolved repeated biogas burner lockouts at an industrial sewage treatment facility. The Dunphy dual-fuel burner uses biogas produced on site, with diesel as backup.

The breakdown
During biogas operation the burner repeatedly locked out on butterfly valve movement errors. The customer faced reliance on purchased diesel instead of using biogas recovered from the treatment process.
Fault diagnosis
Investigation confirmed the servo motor was working correctly, but the biogas butterfly valve was completely seized. Biogas contaminants, including moisture and hydrogen sulphide, can contribute to corrosion, deposits and mechanical sticking.

The repair
We removed the butterfly valve, cleaned and lubricated its appropriate moving components, then refitted it with the existing servo motor. Using burner commissioning mode, we tested movement across the required operating range and returned the boiler to service on biogas.

The result
Biogas operation was successfully restored. This reduced reliance on expensive diesel backup fuel and avoided unnecessary replacement of a serviceable servo motor.

Preventing future biogas valve failures
We recommend a planned inspection and maintenance programme for the biogas fuel train, tailored to gas quality, operating hours and manufacturer instructions. Checks should include valve travel and actuator feedback, mechanical resistance, evidence of deposits or corrosion, gas filtration and condensate management, and trend reviews of burner movement faults. Valve cleaning and lubrication must only use materials and procedures approved for the particular valve and biogas service. After any work, appropriate tightness, safety interlock and combustion checks should be completed by competent engineers before return to service.
Industrial combustion engineering
AH Control Ltd specialises in industrial burner breakdowns, dual-fuel systems, combustion controls and commissioning. We fix what others can’t. Contact us at www.ahcontrol.com.